Summer 2008
Web version | www.jadelearning.com

The 2005 NEC and 2008 NEC, Side by Side

2005 NEC 2008 NEC
Arc-Fault Circuit-Interrupter Protection required in dwelling unit bedrooms.
Combination Type Arc-Fault Circuit-Interrupter Protection required throughout the dwelling unit (except in kitchens, bathrooms, garages and outdoors).
Ampacity of Service Entrance (SE) cable sized from 75 degree column of Table 310.16.

Ampacity of Service Entrance (SE) cable sized from 60 degree column of Table 310.16.

Residential Main Power Feeder sized from residential service conductor table, 310.15(B)(6). Residential feeders must carry 100% of the dwelling unit service load to use Table 310.15(B)(6). Otherwise use Table 310.16.
Multi-wire branch circuits: No simultaneous disconnect required. No grouping of wires required.

Multi-wire branch circuits: Simultaneous disconnect required.  Grounded and ungrounded wires must be grouped together by wire ties or similar means.

Standard 15- and 20-ampere, 125- and 250-volt nonlocking receptacles can be used both indoors and outdoors. Weather resistant receptacles required in wet and damp locations for 15- and 20-ampere, 125- and 250-volt nonlocking receptacles.
Dwelling unit receptacle outlets are either of the 15- and 20-ampere, 125-volt standard type or GFCI protected.

All dwelling unit receptacle outlets must be listed tamper-resistant.

Changes indicated by a line or bullet in the margin. Changes indicated by highlighting.
Indoor fluorescent luminaires will require an individual disconnecting means starting January 1, 2008. Indoor fluorescent luminaires now require an individual disconnecting means, except in dwelling units and industrial locations.

 

 

Back to Newsletter